1.4 Fan Speed Control for Indoor Unit
Outline Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.
The airflow rate can be automatically controlled depending on the difference between the room
thermistor temperature and the target temperature. This is done through phase control and Hall
IC control.
For more information about Hall IC, refer to the troubleshooting for fan motor on page 89.
Automatic Fan
Speed Control
In automatic fan speed operation, the step “SL” is not available.
= The airflow rate is automatically controlled within this range when the FAN setting
button is set to automatic
.
<Cooling>
The following drawing explains the principle of fan speed control for cooling.
<Heating>
In heating operation, the fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room thermistor temperature and the target
temperature.
Note: 1. During POWERFUL operation, fan rotates at H tap + 80 rpm.
2. The fan stops during defrost operation.
Indoor Unit Quiet
Operation
Forced dropping of the fan tap decreases the airflow rate and reduces airflow noise. (Noise is
reduced by about 3 dB as compared to that in L tap.)
Note:
Airflow rate can not be set.
Since the performance is lowered as compared to that in normal operation (70% under rated
conditions), the room may not be cooled or heated when this operation is used for a long
time.
Indoor unit quiet operation is kept in memory even when the power supply is turned OFF.
The indication remains on the display of the wireless remote controller and the indoor unit
quiet operation works when the power is turned ON again.
Step Cooling Heating
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
(R11681)
(R6834)
(R13860)
Fan speed
+2°C
+1°C
0°C
MH
M
ML
L
Room thermistor temperature – target temperature
+3°C