SiBE04-624_B Field Settings
Trial Operation and Field Settings 149
4. Field Settings
4.1 Humidifying Hose Length Setting
Outline Set the humidifying hose length to ensure humidifying capacity. Use the remote controller to set
the humidifying hose length. Power on the unit to establish the communication between the unit
and the remote controller.
(The humidifying hose length includes the rear part of the indoor unit.)
Detail
Note:
If you set the wrong humidifying hose length, select on the step 4) to cancel the
setting.
When setting the humidifying hose length without powering on the indoor unit, the display
shows on the step 5) but the remote controller remembers the set hose length.
When the customer turns the indoor unit on, the hose length information is sent to the indoor
unit.
(R14036)
[CLOCK] button
Display
[SELECT] button
1) Press the [CLOCK] button for 5 seconds.
→ is displayed.
2) Press the [SELECT]
or
button and select .
3) Press the [CLOCK] button to activate the hose length setting mode.
→ The display shows the preset hose length.
When the hose length is not set, is displayed.
4) Press the [SELECT]
or
button and select hose length.
You can select hose length from [~ 3 m] [3.1 ~ 4 m] [4.1 ~ 6 m] [6.1 ~ 8 m] [8.1 ~ 10 m].
5) Press the [CLOCK] button to set the hose length.
6) To return to the normal mode, press the [CLOCK] button for 5 seconds or leave the remote
controller for 60 seconds.