8. INSTALLING THE DUCT
• Connect the duct (field supplied) as shown below.
(Refer to Fig. 14)
<Air inlet side>
• Connect the duct to the inlet flange (field supplied).
• Wrap the inlet flange and the duct connection with aluminum
tape or something similar to prevent air escaping.
<Air outlet side>
•
Connect the duct to the outlet flange (attached with main body).
• Wrap the outlet flange and the duct connection with alumi-
num tape or something similar to prevent air escaping.
• Connect the outlet flange and the unit using the screws
(accessory 8)).
NOTES
• Air filter is not standard accessory, but please mount it in the
duct system of the air inlet side. Select its colorimetric
method (gravity method) 50% or more.
•
Make sure there is a downward slope on the air inlet side of the
duct. This is to prevent rainwater from getting inside the unit.
• Connect the duct so that the unit draws in outside air in the
inlet side. Otherwise, the unit may not work.
• Insulate the duct to prevent condensate from forming.
(Material: glass wool or polyethylene foam, 25 mm thick)
• Use electric insulation between the duct and the wall when
using metal ducts to pass metal or wire laths or metal plating
into wooden buildings.
9. ELECTRIC WIRING WORK
9-1 GENERAL INSTRUCTIONS
• All field supplied parts and materials and electric works must
conform to local codes.
• Use copper wire only.
• For electric wiring work, refer to also “WIRING DIAGRAM”
label attached to the electric parts box lid.
• For remote controller wiring details, refer to the installation
manual attached to the remote controller.
• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each
indoor unit as unit A, unit B..., and be sure the terminal board
wiring to the outdoor unit is properly matched. If wiring and
piping between the outdoor unit and the indoor unit are mis-
matched, the system may cause a malfunction.
• A circuit breaker capable of shutting down power supply to
the entire system must be installed.
• Refer to the installation manual attached to the outdoor unit
for the size of power supply wire connected to the outdoor
unit, the capacity of the circuit breaker and switch, and wire
instructions.
• Be sure to ground the unit.
• Do not connect the ground wire to gas and water pipes, light-
ning rods, or telephone ground wires.
• Gas pipes : might cause explosions or fire if gas leaks.
•
Water pipes : no grounding effect if hard vinyl piping is used.
• Telephone ground wires or lightning rods : might cause
abnormally high electric potential in the ground during
lightning.
9-2 ELECTRICAL CHARACTERISTICS
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A)
9-3 SPECIFICATIONS FOR FIELD SUPPLIED
FUSES AND WIRE
NOTES
1. Select the particular size of electrical wire for power supply
wire in accordance with the standards of the given nation
and region.
2. Allowable length of transmission wire between indoor/out-
door units and between the indoor unit and the remote con-
troller is as follows.
(1) Outdoor unit – Indoor unit:
Max. 1000 m (Total wiring length: 2000 m)
(2) Indoor unit – Remote controller:
Max. 500 m
(3) Max. branches No. of branches :16
3. Insulated thickness: 1mm or more
4. Up to 16 branches are possible for unit-to unit cabling. No
branch is allowed after first branch. (Refer to Fig. 15)
Insulation
(Field supplied)
Inlet flange
(Field supplied)
Outlet flange
(Attached with main body)
Insulation
(Field supplied)
Air outlet side
Air inlet side
Main body
(Downward slope)
Hood
(Field supplied)
Canvas duct
(Field supplied)
Canvas duct
(Field supplied)
Fig. 14
Outer
wall
Units Power supply Fan motor
Model Hz Volts
Voltage
range
MCA MFA kW FLA
FXMQ125MFV1
FXMQ125MFV7
50
220-
240
Max. 264
Min. 198
1.9 15 0.380 1.5
FXMQ200MFV1
FXMQ200MFV7
3.3 15 0.380 2.6
FXMQ250MFV1
FXMQ250MFV7
3.8 15 0.380 3.0
Model
Power supply wire
Remote controller wire
Transmission wire
Field fuses
Wire Size Wire Size
FXMQ125MFV1
FXMQ125MFV7
15A
H05VV-
U3G
Size must
comply
with local
codes.
Sheathed
wire
(2 wire)
0.75 -
1.25
mm
2
FXMQ200MFV1
FXMQ200MFV7
FXMQ250MFV1
FXMQ250MFV7
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2
Branch
Subbranching
Fig. 15