
6 English
FXMQ200 · 250MFV1
1.
Insulate the liquid pipe using the insulation for fitting (Accessory
2)).
(Tighten both edges with clamping material.)
2. Use the attached pipe (Accessory 1)) for connecting the
gas pipes and make sure to insulate the gas pipes (using
field supplied insulation) all the way to the base where they
connect to the unit.
3. The turning torque of the hexagon head bolts (Accessory
7)) to connect the attached pipe (Accessory 1)) to the unit is
21.5 – 28.9 N/m.
CAUTION
Be sure to insulate any field pipe all the way to the pipe con-
nection inside the unit. Any exposed pipe may cause
cndensate or burns if touched.
CAUTION
CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING
Do not use flux when brazing refrigerant piping. Therefore,
use the phosphor copper brazing filler metal (BCuP-2:JIS z
3264/B-Cu93P-710/795: ISO 3677) which does not require
flux.
(Flux has extremely harmful infulence on refrigerant piping
systems. For instance, if the chlorine based flux is used, it
will cause pipe corrosion or, in particular, if the flux contains
fluorine, it will damage the refrigerant oil.)
• Before brazing local refrigerant piping, nitrogen gas shall be
blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large
amount of oxide film develops inside the piping, and could
cause system malfunction.
• When brazing the refrigerant piping, only begin brazing after
having carried out nitrogen substitution or while inserting
nitrogen into the refrigerant piping. Once this is done, con-
nect the unit with a flared or a flanged connection.
•
Nitrogen should be set to 0.02 MPa with a pressure-reducing
valve if brazing while inserting nitrogen into the piping.
7. DRAIN PIPING WORK
〈〈Rig the drain pipe as shown below and take measures
against condensate. Improperly rigged piping could lead to
leaks and eventually wet furniture and belongings.〉〉
〈〈Insulate the drain pipes inside the building and the drain
sockets.〉〉
(1) Carry out the drain piping.
•
The drain pipe should be short with a downward slope lower
than 1/100 and should prevent air pockets from forming.
• The diameter of the pipe is the same as that of the con-
necting pipe (PS1B), and should be kept equal to or
greater than that of the connecting pipe.
NOTE
•
If converging multiple drain pipes, install according to the pro-
cedure shown below. (Select an appropriate central drain
pipe thickness for the units they will be connected to.)
(2)
After piping work is finished, check drainage flow smoothly.
• Open the water supply port, add approximately 1 litre of
water slowly into the drain pan and check drainage flow.
(Refer to Fig. 13)
Pools of drainage can cause the drain pipes to clog.
CAUTION
• Do not connect the drain pipe directly to sewage pipes that
smell of ammonia. The ammonia in the sewage might enter
the unit through the drain pipes and corrode the heat
exchanger.
Fig. 10
Insulation
(Field supplied)
Insulation
(Field
supplied)
Attached pipe
(Accessory 1))
Eliminate
a gap
Eliminate
a gap
Main body
Main body
Insulation
(Attached with
main body)
Insulation
(Attached with
main body)
Spring washer (Accessory 6))
Hexagon head bolt (Accessory 7))
Insulation for fitting
(Accessory 2))
Clamps
(Accessory10))
Flare nut
Gas
pipe
Liquid
pipe
Nitrogen
Refrigerant
piping
Part to be
brazed
Taping
Pressure-reducing valve
hands
valve
Nitrogen
Fig. 11
Central drain pipe
100mm
or more
(Install with a downward slope of at least 1/100)
Fig. 12
Water supply port
Fig. 13
Comentarios a estos manuales