English 9
10-2 WIRING EXAMPLE
Fit the power supply wiring of each unit with a switch and
fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE (3 SYSTEMS)
1. When using 1 remote controller for 1 indoor unit. (Nor-
mal operation)
2. For group control or control by 2 remote controllers
[ PRECAUTIONS ]
1. A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.
10-3
CONTROL BY 2 REMOTE CONTROLLERS (Con-
trolling 1 indoor unit by 2 remote controllers)
When using 2 remote controllers, one must be set to
MAIN and the other to SUB.
MAIN/SUB CHANGEOVER
(1) Insert a screwdriver into the recess between the upper
and lower part of remote controller and, working from the 2
positions, pry off the upper part.
(The remote controller PC board is attached to the upper
part of remote controller.)
(2) Turn the MAIN/SUB changeover switch on one of the two
remote controller PC boards to S.
(Leave the switch of the other remote controller set to M.)
Wiring Method (See 10-1.)
(1) Remove the electric parts box lid.
(2) Add the second remote controller (slave) to the trans-
mission terminal block (X2M/P1, P2) in the electric
parts box. (There is no polarity.)
(Refer to Fig. 20 and 9-3.)
10-4 COMPUTERISED CONTROL (FORCED OFF
AND ON/OFF OPERATION)
(1) Wire specifications and how to perform wiring
Connect the input from outside (Input A) to terminals T1
and T2 of the transmission terminal block (X2M).
Power supply wire
Transmission wire
Switch
Fuse
Power supply
Main
switch
Remote controller
Indoor unit
Fig. 18
Outdoor unit
LN
LN
IN/D OUT/D
F
1 F2 F1 F2
Control box
LN
LN
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2LN
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2LN LN
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2
LN
Outdoor unit
Unit A
Unit B
Unit C
Most
downstream
unit
Power supply
220-240V
50Hz
Power supply
220-240V
50Hz
Power supply
220-240V
50Hz
Power supply
220-240V
50Hz
Fig. 19
Unit A
IN/D OUT/D
F
1 F2 F1 F2
Control box
LN
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2 LN
P
1
P
2
F
1
F
2
T
1
T
2 LN
P
1
P
2
F
1
F
2
T
1
T
2 LN
P
1
P
2
F
1
F
2
T
1
T
2
P
1
P
2
P
1
P
2
LN
Outdoor unit
Unit B
Unit C
Most
downstream
unit
Control by 2
remote controllers
Power supply
220-240V
50Hz
Note: It is not necessary to designate
indoor unit address when using
group control.
The address is automatically set
when power is activated.
Fig. 20
Wire specification Sheathed vinyl cord or cable (2 wire)
Size
0.75 - 1.25 mm
2
Length Max. 100 m
External terminal
Contact that can ensure the minimum appli-
cable load of 15 V DC, 1 mA.
Upper part of
remote controller
Lower part of
remote controller
Insert the screwdriver here and gently work
off the upper part of remote controller.
Only one remote
controller needs to be
changed if factory
settings have
remained untouched.
(Factory setting)
S
M
S
S
M
Remote controller
PC board
F2 T1 T2
FORCED
OFF
Input A
Vista de pagina 10
1 2 ... 6 7 8 9 10 11 12 13

Comentarios a estos manuales

Sin comentarios