6. REFRIGERANT PIPING
For refrigerant piping between outdoor unit and this unit,
see the installation manual attached to the outdoor unit.
(Refer to Table 1)
Execute heat insulation work completely on both sides of
the gas pipe and the liquid pipe. Otherwise, a water leakage
can result sometimes.
When using a heat pump, the temperature of the gas pipe
can reach up to approximately 120°C, so use insulation
which is sufficiently resistant.
Improve the insulation on the refrigerant piping depending
on the installation environment. If the insulation is not suffi-
cient, condensate may form on the surface of the insulation.
Before refrigerant piping work, check which type of refrig-
erant is used. Proper operation is not possible if the types
of refrigerant are not the same.
CAUTION
Use a pipe cutter and flare suitable for the type of refrig-
erant.
Apply ester oil or ether oil around the flare portions
before connecting. (Refer to Fig. 7)
To prevent dust, moisture or other foreign matter from
infiltrating the tube, either pinch the end or cover it with
tape.
Do not allow anything other than the designated refrig-
erant to get mixed into the refrigerant circuit, such as air,
etc. If any refrigerant gas leaks while working on the
unit, ventilate the room thoroughly right away.
The outdoor unit is charged with refrigerant.
Be sure to use both a spanner and torque wrench together,
as shown in the drawing, when connecting or disconnecting
pipes to/from the unit. (Refer to Fig. 8)
Refer to Table 2 for the dimensions of flare nut spaces.
When connecting the flare nut, coat the flare section (both
inside and outside) with ester oil or ether oil, rotate three or
four times first, then screw in. (Refer to Fig. 7)
Refer to Table 2 for tightening torque.
Table 1
Table 2
NOTE
Use the flare nuts attached with the unit.
CAUTION
Over-tightening may damage the flare and cause a refriger-
ant leakage.
Not recommendable but in case of emergency
You must use a torque wrench but if you are obliged to
install the unit without a torque wrench, you may
follow the installation method mentioned below.
After the work is finished, make sure to check that
there is no gas leak.
When you keep on tightening the flare nut with a spanner,
there is a point where the tightening torque suddenly
increases. From that position, further tighten the flare nut
the angle shown below:
Tabl e 3
After checking the pipe-connection for gas leakage, be sure
to insulate the liquid and gas pipe, referring to Fig.9, 10 and
the following points.
FXMQ125MFV1
1. Insulate the liquid and gas pipes using the insulation for fit-
ting (Accessory 2), 3))
(Tighten both edges with clamping material.)
2. Make sure the insulation for fitting (Accessory 3)) on the
gas pipe has its seams facing up.
3.
For the gas pipe, wrap the sealing pad (Accessory 4)) around
the insulation for fitting (Accessory 3)) (flare nut part).
Unit to be connected Gas pipe diameter
Liquid pipe
diameter
FXMQ125MFV1
FXMQ125MFV7
φ15.9 φ9.5
FXMQ200MFV1
FXMQ200MFV7
φ19.1 Use attached pipe. φ9.5
FXMQ250MFV1
FXMQ250MFV7
φ22.2 Use attached pipe. φ9.5
Pipe
size
Tightening torque
Flare dimen-
sions
A (mm)
Flare shape
φ
9.5
(3/8)
32.7 39.9N·m 12.8 13.2
φ
15.9
(5/8)
61.8 75.4N·m 19.3 19.7
A
45
0
±
2
0
R0.4-0.8
90
0
±
2
0
Pipe size
Further tightening
angle
Recommended arm length of
tool
φ 9.5 (3/8) 60 to 90 degrees Approx. 200mm
φ 15.9 (5/8) 30 to 60 degrees Approx. 300mm
Ester oil or ether oil.
Fig. 7
Torque wrench
Spanner
Piping union
Flare nut
Fig. 8
Insulation
(Attached with main body)
Insulation
for fitting
(Accessory 3))
Sealing pad
(Accessory 4))
Eliminate a gap
Main body
Main body
Clamps (Accessory 10))
Flare nut
Insulation (Field supplied)
Eliminate a gap
Insulation for fitting
(Accessory 2))
Insulation
(Attached with
main body)
Clamps
(Accessory 10))
Flare nut
Insulation
(Field supplied)
Gas pipe
Liquid
pipe
Fig. 9