8 English
10. WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER
10-1 HOW TO CONNECT THE WIRES
(Remove the electric parts box lid and wire as shown in the figure 16, 17.)
• Power supply wire, Ground wire (Refer to Fig. 17)
Connect the wire to L and N on the power supply terminal
block (X1M). Also, connect the ground wire to the ground ter-
minal. Take the power supply wire and the ground wire into
the unit through the wiring through hole <1>, and firmly
secure them together using the clamp (Accessory 10)).
•
Transmission wire, Remote controller wire (Refer to Fig. 17)
Connect the transmission wire to F1 and F2 on the transmis-
sion terminal block (X2M). Connect the remote controller
wire to P1 and P2 on the transmission terminal block (X2M).
Take them into the unit through the wiring through hole <2>,
and firmly secure the wires using the clamp (Accessory 10)).
CAUTION
• Wire the electric parts box so that the wiring is at least 10 mm
above the bottom of the electric parts box.
•
Be sure to attach the sealing material or putty (field supplied) to
the wiring through holes to prevent the infiltration of water as well
as any insects and other small creatures from outside. Other-
wise a short-circuit may occur inside the electric parts box.
• When clamping the wires, be sure no pressure is applied to
the wire connections by using the included clamping material
to make appropriate clamps. Also, when wiring, make sure
the lid on the electric parts box fits snugly by arranging the
wires neatly and attaching the electric parts box lid firmly.
When attaching the electric parts box lid, make sure no wires
get caught in the edges. Pass wire through the wiring through
holes to prevent damage to them.
• Make sure the remote controller wire, the transmission wire
and power supply wire, ground wire do not pass through the
same locations outside of the unit, separating them by at
least 50mm, otherwise electrical noise (external static) could
cause mistaken operation or breakage.
[ PRECAUTIONS ]
1. Use round crimp-style terminals for connecting wires to the
power supply terminal block.
If unavailable, observe the following points when wiring.
• Do not connect wires of different gauge to the same
power supply terminal.
(Looseness in the connection may cause overheating.)
• Use the specified electric wire. Connect the wire securely
to the terminal. Lock the wire down without applying
excessive force to the terminal.
2. Tightening torque for the terminal screws.
• Use the correct screwdriver for tightening the terminal
screws. If the blade of screwdriver is too small, the head
of the screw might be damaged, and the screw will not be
properly tightened.
• If the terminal screws are tightened too hard, screws
might be damaged.
• Refer to the table below for the tightening torque of the
terminal screws.
3. Do not connect wires of different gauge to the same ground
terminal. Looseness in the connection may deteriorate pro-
tection.
4. Outside of the unit, keep transmission wire and remote con-
troller wire at least 50 mm away from power supply wire and
ground wire. The unit may malfunction if subjected to elec-
trical noise (external static).
5. For remote controller wiring, refer to the “INSTALLATION
MANUAL OF REMOTE CONTROLLER” attached to the
remote controller.
6. Never connect power supply wire to the transmission
terminal block (X2M). A mistake of the sort could dam-
age the entire system.
7. Use only specified wire and tightly connect wires to termi-
nals. Be careful wires do not place external stress on termi-
nals. Keep wiring in neat order and so as not to obstruct
other equipment such as the electric parts box lid. Make
sure the lid closes tight. Incomplete connections could
result in overheating, and in worse case, electric shock or
fire.
Remote controller
wire
Transmission
terminal block (X2M)
Power supply
terminal block (X1M)
Power supply
wire
Ground wire
Electric parts box lid
Fig. 16
Transmission
wire
LN
Electric parts box
X3M
A1P
X1M
X2M
Ground
terminal
Wiring
through
hole <1>
Wiring
through
hole <2>
Clamp
(Accessory 10))
Clasp
Fig. 17
Electric wire
Round crimp-style terminal
Attach insulation sleeve
Terminal Size Tightening torque
Transmission terminal block (X2M) M3.5 0.79 – 0.97 N·m
Power supply terminal block (X1M)
Ground terminal
M4
M5
1.18 – 1.44 N·m
3.02 – 4.08 N·m
Comentarios a estos manuales