4 English
2-3 OPTIONAL ACCESSORIES
• The optional remote controller is required for this indoor unit.
•
Select a remote controller from Table 1 according to customer request and install in an appropriate place.
(For installation, follow the installation manual included with the remote controllers.)
Table 1
• If the customer wishes to use a remote controller that is not listed above, select a suitable remote
controller after consulting catalogs and technical guide.
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND
CHECK AFTER INSTALLATION IS FINISHED.
1. Items to be checked after completion of work
Name
(11) Screws
(M4 × 10)
(12) Screws
(M5 × 12)
(13) Remote
controller wiring
(Other)
• Operation manual
• Installation manual
*1)
The bracket for installation
is screwed onto the main
unit (top plate).
*2) These parts are used
when the remote
controller is installed in
the main unit.
Quantity 3 pcs. *2) 2 pcs. 1 pc. *2)
Shape
Remote controller
Wired type BRC1E52A7/BRC1E51A7/BRC1D528
Items to be checked If not properly done, what is likely to occur Check
Are the indoor unit and outdoor unit fixed
firmly?
The unit may drop, vibrate or make noise.
Is the installation of the indoor unit and the
outdoor unit completed?
The unit may malfunction or the components
may burn out.
Is the gas leakage checked with the
leakage test pressure written in the
installation manual supplied with the
outdoor unit?
It may result in insufficient cooling or heating.
Is the unit fully insulated? (Refrigerant
piping, drain piping)
Condensate water may drip.
Does drainage flow smoothly? Condensate water may drip.
Does the power supply voltage correspond
to that shown on the name plate?
The unit may malfunction or the components
may burn out.
Are wiring and piping correct?
The unit may malfunction or the components
may burn out.
Is the unit safely grounded? It may result in electric shock.
Is wiring size according to specifications?
The unit may malfunction or the components
may burn out.
Is something blocking the air outlet or inlet
of either the indoor or outdoor units?
It may result in insufficient cooling or heating.
(This can lead to malfunction or decreased
performance due to decreased air volume.)
Are refrigerant piping length and additional
refrigerant charge noted down?
The refrigerant charge in the system is not clear.