18 English
8-2 SPECIFICATIONS FOR FIELD WIRE
For the wiring of the outdoor unit, refer to the installation manual attached to the outdoor unit.
Remote controller and transmission wiring are field supplied. (Refer to Table 4)
Wiring specifications are shown on the condition that the wiring has a voltage drop of 2%.
Table 4
*This will be the total extended length in the system when doing group control.
NOTE
1. It shows the case when conduit pipes are used. When the conduit pipes are not used, use H07RN-F.
2. Sheathed vinyl cord or cable (insulation thickness: 1mm or more)
9. HOW TO CONNECT WIRINGS AND WIRING EXAMPLE
9-1 HOW TO CONNECT WIRINGS
Wire
Size (mm
2
)
Length
Wiring the units
H05VV-U4G
(NOTE 1)
2.5
Remote controller cord
Vinyl cord with sheath or
cable (2 wire) (NOTE 2)
0.75 - 1.25 Max. 500m *
Fig. 30
Fig. 29
Earth terminal
Earth terminal
Outdoor unit
(Terminal block) (Terminal block)
Indoor unit
Clamp (8)
(accessory)
Wiring
diagram
Control box lid
Wiring lead-in port
Inter unit wire for the indoor and
outdoor units and earth wire
Power supply
terminal block
(X2M:3P)
Wiring the units
Earth wire
Pipe retainer
Align the numbers.
How to connect the inter unit wiring for
the indoor and outdoor units
123
Do not perform solder finishing.
1
2
3
1
2
3
3P249378-4D_FM6.book Page 18 Thursday, December 15, 2011 10:00 AM