Performance Data
Model: FDMQN100CXV1 - RQ90DXY1
Heating Mode
ID DB
Outdoor WB
-9°C -6°C -5°C 6°C 12°C 15°C 18°C
TC SC TC SC TC SC TC SC TC SC TC SC TC SC
15°C 6.378 6.378 7.219 7.219 7.499 7.499 10.583 10.583 12.264 12.264 13.105 13.105 13.946 13.946
17°C 6.211 6.211 7.497 7.497 7.331 7.331 10.570 10.570 12.091 12.091 12.931 12.931 13.771 13.771
19°C 6.044 6.044 7.774 7.774 7.163 7.163 10.557 10.557 11.918 11.918 12.757 12.757 13.596 13.596
21°C 5.877 5.877 7.670 7.670 6.994 6.994 10.408 10.408 11.744 11.744 12.583 12.583 13.421 13.421
23°C 5.710 5.710 7.184 7.184 6.826 6.826 10.123 10.123 11.571 11.571 12.408 12.408 13.246 13.246
25°C 5.542 5.542 6.697 6.697 6.658 6.658 9.838 9.838 11.398 11.398 12.234 12.234 13.071 13.071
27°C 5.375 5.375 6.211 6.211 6.489 6.489 9.553 9.553 11.224 11.224 12.060 12.060 12.896 12.896
Frost Region
Remark:
AFR: Air ow rate (CFM)
EWB: Entering Wet Bulb Temp. (°C)
EDB: Entering Dry Bulb Temp. (°C)
TC: Total Cooling / Heating Capacity (kW)
SC: Sensible Cooling / Heating Capacity (kW)
PI: Power Input (kW)
Notes:
1. Ratings shown are net capacities.
2. shows nominal capacities.
3. Direct interpolation is permissible. Do not extrapolate.
4. Unit is able to operate at ambient from 19°C to 46°C DB (cooling) / -9°C to 18°C WB (heating) without pressure trip.