34
Engineering & Physical Data
Safety Device
MODEL
INDOOR
FDMRN25CXV1 FDMRN35CXV1 FDMRN50CXV1
OUTDOOR
RN25CXV1 RN35CXV1 RN50CXV1
SAFETY
DEVICE
HIGH PRESSURE SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
LOW PRESSURE SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
PHASE SEQUENCER N/A
DISCHARGE THERMOSTAT SETTING ˚C / ˚F N/A
MODEL
INDOOR
FDMRN60CXV1 FDMRN50CXV1 FDMRN60CXV1
OUTDOOR
RN60CXV1 RN50CXY1 RN60CXY1
SAFETY
DEVICE
HIGH PRESSURE SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
LOW PRESSURE SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
PHASE SEQUENCER N/A YES
DISCHARGE THERMOSTAT SETTING ˚C / ˚F N/A 130 / 266
MODEL
INDOOR
FDMRN71CXV1 FDMRN100CXV1
OUTDOOR
RR71CXV1 RR71CXY1 RR90DXV1
SAFETY
DEVICE
HIGH PRESSURE SWITCH
TYPE N/A NC
OPEN kPa / psi N/A 4137 / 600
CLOSE kPa / psi N/A 3310 / 480
LOW PRESSURE SWITCH
TYPE N/A NC
OPEN kPa / psi N/A 48 / 7
CLOSE kPa / psi N/A 152 / 22
PHASE SEQUENCER N/A YES N/A
DISCHARGE THERMOSTAT SETTING ˚C / ˚F N/A 130 / 266 N/A
MODEL
INDOOR
FDMRN100CXV1 FDMRN100CXV1
OUTDOOR
RR90DXY1 RR100DXV1 RR100DXY1
SAFETY
DEVICE
HIGH PRESSURE SWITCH
TYPE NC
OPEN kPa / psi 4137 / 600
CLOSE kPa / psi 3310 / 480
LOW PRESSURE SWITCH
TYPE NC
OPEN kPa / psi 48 / 7
CLOSE kPa / psi 152 / 22
PHASE SEQUENCER YES N/A YES
DISCHARGE THERMOSTAT SETTING ˚C / ˚F 130 / 266 N/A 130 / 266
MODEL
INDOOR
FDMRN125CXV1 FDMRN140CXV1
OUTDOOR
RR125DXY1 RR140DXY1
SAFETY
DEVICE
HIGH PRESSURE SWITCH
TYPE NC
OPEN kPa / psi 4137 / 600
CLOSE kPa / psi 3310 / 480
LOW PRESSURE SWITCH
TYPE NC
OPEN kPa / psi 48 / 7
CLOSE kPa / psi 152 / 22
PHASE SEQUENCER YES
DISCHARGE THERMOSTAT SETTING ˚C / ˚F 130 / 266
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
DAIKIN_FDMRN.indb 34DAIKIN_FDMRN.indb 34 1/8/2013 8:46:06 AM1/8/2013 8:46:06 AM