35
Engineering & Physical Data
MODEL
INDOOR
FDMQN25CXV1 FDMQN35CXV1 FDMQN50CXV1
OUTDOOR
RYN25CXV1 RYN35CXV1 RYN50CXV1
SAFETY
DEVICE
HIGH PRESSURE SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
LOW PRESSURE SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
PHASE SEQUENCER N/A
DISCHARGE THERMOSTAT SETTING ˚C / ˚F N/A
MODEL
INDOOR
FDMQN60CXV1 FDMQN50CXV1 FDMQN60CXV1
OUTDOOR
RYN60CXV1 RYN50CXY1 RYN60CXY1
SAFETY
DEVICE
HIGH PRESSURE SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
LOW PRESSURE SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
PHASE SEQUENCER N/A YES
DISCHARGE THERMOSTAT SETTING ˚C / ˚F N/A 130 / 266
MODEL
INDOOR
FDMQN71CXV1
FDMQN100CXV1
OUTDOOR
RQ71CXV1 RQ71CXY1 RQ90DXV1
SAFETY
DEVICE
HIGH PRESSURE SWITCH
TYPE N/A NC
OPEN kPa / psi N/A 4137 / 600
CLOSE kPa / psi N/A 3310 / 480
LOW PRESSURE SWITCH
TYPE N/A NC
OPEN kPa / psi N/A 48 / 7
CLOSE kPa / psi N/A 152 / 22
PHASE SEQUENCER N/A YES N/A
DISCHARGE THERMOSTAT SETTING ˚C / ˚F N/A 130 / 266 N/A
MODEL
INDOOR
FDMQN100CXV1
FDMQN100CXV1
OUTDOOR
RQ90DXY1 RQ100DXV1 RQ100DXY1
SAFETY
DEVICE
HIGH PRESSURE SWITCH
TYPE NC
OPEN kPa / psi 4137 / 600
CLOSE kPa / psi 3310 / 480
LOW PRESSURE SWITCH
TYPE NC
OPEN kPa / psi 48 / 7
CLOSE kPa / psi 152 / 22
PHASE SEQUENCER YES N/A YES
DISCHARGE THERMOSTAT SETTING ˚C / ˚F 130 / 266 N/A 130 / 266
MODEL
INDOOR
FDMQN125CXV1 FDMQN140CXV1
OUTDOOR
RQ125DXY1 RQ140DXY1
SAFETY
DEVICE
HIGH PRESSURE SWITCH
TYPE NC
OPEN kPa / psi 4137 / 600
CLOSE kPa / psi 3310 / 480
LOW PRESSURE SWITCH
TYPE NC
OPEN kPa / psi 48 / 7
CLOSE kPa / psi 152 / 22
PHASE SEQUENCER YES
DISCHARGE THERMOSTAT SETTING ˚C / ˚F 130 / 266
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.