Daikin FTKD60BVMA Especificaciones Pagina 118

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 224
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 117
SiEN04-306D Troubleshooting
Service Diagnosis 109
4.3 Freeze-up Protection Control or High Pressure Control
remote control
Display
A5
Method of
Malfunction
Detection
High pressure control (heat pump model only)
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is used for the high pressure control (stop, outdoor fan stop, etc.)
The freeze-up protection control (operation halt) is activated during cooling operation
according to the temperature detected by the indoor unit heat exchanger thermistor.
Malfunction
Decision
Conditions
High pressure control
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is above 65°C
Freeze-up protection
When the indoor unit heat exchanger temperature is below 0°C during cooling operation.
Supposed
Causes
Operation halt due to clogged air filter of the indoor unit.
Operation halt due to dust accumulation on the indoor unit heat exchanger.
Operation halt due to short-circuit.
Detection error due to faulty indoor unit heat exchanger thermistor.
Detection error due to faulty indoor unit PCB.
Vista de pagina 117
1 2 ... 113 114 115 116 117 118 119 120 121 122 123 ... 223 224

Comentarios a estos manuales

Sin comentarios