14
NG
OK
NO
OK
YES
YES
NG
NO
ON
Blinks
Is LED-A turned on by turning the
power supply back on?
Is indoor unit data displayed with transmissio
n
monitor connected to terminal board of eithe
r
indoor or outdoor unit?
Replace the indoor unit PC board.
(If two numbers of PC boards are provided,
refer to the service manual of applicable
model for the replacement.)
Carry out grounding work.
Take measures against noise.
Example:
a) Large capacity electric heater (wit
h
temperature control)
b) Welder
c) Inverter fan (used for ventilation, etc.)
Is grounding work completed?
Is there any noise source?
Normal (Note)
Is correct power supply voltage
supplied?
Recheck the power supply.
Malfunction 7-1:Indoor Unit LED-A On
Possible
causes
Ԙ Faulty indoor unit PC board
ԙ Malfunction of microcomputer
(Note) Be careful that, even when LED-A starts blinking normally after the power supply is turned back
on, this malfunction may reoccur within a few minutes to a few days.
(Reference) The microcomputer for PC boards is not programmed to turn LED-A on. The program may not be
functioned while LED-A is ON as it repeats ON/OFF operation (blinks).