3
1
3
• Split Sky Air • Outdoor Units
10
• Outdoor Units • R-410A • RKS-E2V1B
3 Electrical data
Representative unit combination Power supply Comp. OFM IFM
Indoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FLKS25BAVMB RKS25E2V1B
50 - 220
50 - 230
50 - 240
Max. 50Hz 264V
Min. 50Hz 198V
9.75 10 50
3.2
23 0.16 34 0.343.1
2.9
3D055010B
SYMBOLS
MCA : Min. Circuit Amps (A)
MFA : Max. Fuse Amps (A)
RHz : Rated operating frequency (Hz)
RLA : Rated Load Amps (A)
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps (A)
W : Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on
the document title of your choice.
Representative unit combination Power supply Comp. OFM IFM
Indoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA
FDKS25EAVMB RKS25E2V1B
50 - 220
50 - 230
50 - 240
Max. 50Hz 264V
Min. 50Hz 198V
9.75 10 54.5
3.5
23 0.16 62 0.53.3
3.2
3D055010B
SYMBOLS
MCA : Min. Circuit Amps (A)
MFA : Max. Fuse Amps (A)
RHz : Rated operating frequency (Hz)
RLA : Rated Load Amps (A)
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps (A)
W : Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on
the document title of your choice.