Installation manual
11
REMQ8P9 + REMQ10~16P8 + REMHQ12P8Y1B
VRVIII System air conditioner
4PW48463-1A
7. LEAK TEST AND VACUUM DRYING
The units were checked for leaks by the manufacturer.
After connecting the field piping, perform the following inspections.
1 Preparations
Referring to figure 23, connect a nitrogen tank, a refrigerant tank
and a vacuum pump to the outdoor unit and perform the
airtightness test and the vacuum drying.
The refrigerant tank and the charge hose connected to the
refrigerant charge port or valve A are needed to perform
refrigerant charging.
2 Airtightness test and vacuum drying
Airtightness test:
Pressurize the liquid pipe, the suction gas pipe, the high
pressure/low pressure gas pipe and the equalizer pipe from the
service ports of each stop valve to 4.0 MPa (40 bar) (do not
pressurize more than 4.0 MPa (40 bar)). If the pressure does not
drop within 24 hours, the system passes the test. If the pressure
drops, check where the nitrogen leaks from.
Note 1 When the equivalent pipe length between outdoor and indoor units is 90 m or more, the size of the main
liquid pipe must be increased. Never increase suction gas pipe and HP/LP gas pipe sizes.
Depending on the length of the piping, the capacity may drop, but even in such a case it is possible to
increase the size of the main liquid pipe.
Note 2 Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to 90 m if all the following conditions are fulfilled.
Required conditions Example drawings
It is necessary to increase the pipe size of the liquid and suction gas pipe if the pipe length between the
first and the final branch kit is over 40 m (reducers must be procured on site). Increasing the HP/LP gas
pipe size is not allowed.
If the increased liquid pipe size is larger than the pipe size of the main liquid pipe, then the pipe size of
the main liquid pipe needs to be increased as well.
If the increased suction gas pipe size is larger than the pipe size of the main suction gas pipe, then the
allowable length after the first refrigerant branch kit may not be increased to 90 m.
Size-up of the main suction gas pipe may affect a good oil return to the outdoor unit due to influence of
the HP/LP gas pipe.
indoor unit 8:
b+c+d+e+f+g+p90 m
increase the pipe size
of b, c, d, e, f, g
Increase the pipe size as follows
For calculation of total extension length, the actual length of above pipes must be doubled (except length of
main pipes and of pipes which do not have an increased pipe size).
a+b*2+c*2+d*2+e*2+f*2+g*2
+h+i+j+k+l+m+n+p1000 m
Indoor unit to the nearest branch kit 40 m h, i, j....... p40 m
The difference between the distance of the outdoor unit to the farthest indoor unit and the distance of the
outdoor unit to the nearest indoor unit 40 m
The most remote indoor unit 8
The nearest indoor unit 1
(a+b+c+d+e+f+g+p)–(a+h)40 m
8+10
12~16
9.5 12.7
12.7 15.9
18~24
26~48
15.9 19.1
19.1 22.2
REY(H)Q Ø REY(H)Q Ø
1
6
2
54
3
1 Outdoor unit 4 First refrigerant
branch kit
2 Main pipes
3 Increase only liquid
pipe size
5 BS unit
6 Indoor unit
Gas side Liquid side
REYQ18~22 Ø28.6 Ø31.8
(a)
(a) If not available, increase is not allowed
Ø9.5 Ø12.7
REYQ24 Ø34.9 Ø12.7 Ø15.9
REYQ26~34 Ø34.9 Ø38.1
(a)
Ø15.9 Ø19.1
REYQ36~48 Ø41.3 Ø19.1 Ø22.2
REYHQ16+20+22 Ø28.6 Ø31.8
(a)
REYHQ24 Ø34.9
— Increase is not allowed
ab c d e f
g
H1
p
ABCDEFG
1234567
8
H2
hijklmn
1
2
3
1 Outdoor unit
2 Refnet joints (a~g)
3 Indoor units (1~8)
1 Gauge manifold
2 Nitrogen
3 Measuring instrument
4 Refrigerant R410A tank (siphon system)
5 Vacuum pump
6 Charge hose
7 Equalizer pipe stop valve
8 High pressure/low pressure pipe stop valve
9 Suction gas line stop valve
10 Liquid line stop valve
11 Refrigerant charge port
12 Valve A
13 Valve B
14 Valve C
15 To BS unit or indoor unit
16 Stop valve
17 Service port
18 Field piping
19 Gas flow
NOTE
Make sure to perform airtightness test
and vacuum drying using the service
ports of the stop valves of the
equalizer pipe, HP/LP gas pipe,
suction gas pipe and liquid pipe. (For
the service port location, refer to the
"Caution" label attached on the front
panel of the outdoor unit.)
See "11.3. Stop valve operation procedure" on
page 18 for details on handling the stop valve.
To prevent entry of any contamination and to
prevent insufficient pressure resistance, always
use the special tools dedicated for working with
R410A refrigerant.
NOTE
Make sure to use nitrogen gas.