REMQ8P9 + REMQ10~16P8 + REMHQ12P8Y1B
VRVIII System air conditioner
4PW48463-1A
6.6. Example of connection
Example of connection
(Connection of 8 indoor units)
Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header
Outdoor units installed
in a multiple outdoor
unit system
(REYQ18~48 +
REYHQ16 +
REYHQ20~24)
Install the joint part ( part in the figure) of the outdoor unit multi connection piping kit
horizontally with attention to the installation restrictions described in "connecting the
refrigerant piping".
(*) In case of multi combination, interprete the word "outdoor" as "first outdoor
branch".
Maximum allowable
length
Between outdoor and indoor units
Actual pipe length
Pipe length between outdoor(*) and indoor units ≤165 m
[Example] unit 8: a+b+c+d+e+s≤165 m [Example] unit 6: a+b+l≤165 m,
unit 8: a+m+n+p≤165 m
[Example] unit 8: a+o≤165 m
Equivalent length
Equivalent pipe length between outdoor(*) and indoor units ≤190 m (Assume equivalent pipe length of the refnet joint to be 0.5 m, of the refnet header to be 1.0 m,
of the BSVQ100 and BSVQ160 to be 4 m and of the BSVQ250 to be 6 m (for calculation purposes)) (See note 1)
Total extension length Total piping length from outdoor(*) to all indoor units ≤1000 m
Between the first outdoor unit multi connection piping kit
and outdoor unit (in case of a multiple outdoor unit system)
Actual and equivalent
pipe length
The actual pipe length from the first outdoor unit multi connection piping kit to the outdoor unit ≤10 m. (x≤10 m, y≤10 m, z≤10 m)
The equivalent pipe length from the first outdoor unit multi connection piping kit to the outdoor unit ≤13 m. (x≤13 m, y≤13 m, z≤13 m)
Allowable height
difference
Between outdoor and indoor units Difference in height between outdoor and indoor units (H1)≤50 m (≤40 m if outdoor unit is located in a lower position).
Between indoor and indoor units Difference in height between adjacent indoor units (H2)≤15 m
Between outdoor and outdoor units Difference in height between adjacent outdoor units (H3)≤5 m
Allowable length after the branch Actual pipe length
Pipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit ≤40 m (See note 2)
[Example] unit 8: b+c+d+e+s≤40 m [Example] unit 6: b+l≤40 m, unit 8: m+n+p≤40 m [Example] unit 8: o≤40 m
Outdoor unit multi connection piping kit and refrigerant branch kit selection How to select the refnet joint
When using refnet joints at the first branch counted from the outdoor unit side, choose from
the following table in accordance with the capacity of the outdoor unit (example: refnet joint
A).
How to select the refnet header
Choose from the following table in accordance with the total capacity of all the indoor units connected
below the refnet header.
Note: 250 type indoor unit can not be connected lower than the refnet header.
Outdoor unit
capacity type (Hp)
Refrigerant branch kit name
Indoor
capacity type
Refrigerant branch kit name
3 pipes 2 pipes
8+10 KHRQ23M29T <200 KHRQ23M29H KHRQ22M29H
12~22 KHRQ23M64T 200≤x<290 KHRQ23M29H KHRQ22M29H
≥24 KHRQ23M75T 290≤x<640 KHRQ23M64H KHRQ22M64H
For refnet joints other than the first branch, select the proper branch kit model based on the
total capacity index of all indoor units connected after the refrigerant branch.
≥640 KHRQ23M75H KHRQ22M75H
How to choose an outdoor multi connection piping kit (this is required when the
system is a multiple outdoor unit system)
Indoor
capacity type
Refrigerant branch kit name
3 pipes 2 pipes
Choose from the following table in accordance with the number of outdoor units
<200 KHRQ23M20T KHRQ22M20T
Number of
outdoor units
Branch kit name200≤x<290 KHRQ23M29T9 KHRQ22M29T
290≤x<640 KHRQ23M64T KHRQ22M64T 2 BHFQ23P907
≥640 KHRQ23M75T KHRQ22M75T 3 BHFQ23P1357
Example of downstream indoor units [Example]
in case of refnet joint C: indoor units 5+6+7+8
[Example]
in case of refnet joint B: indoor units 7+8,
in case of refnet header: indoor units 1+2+3+4+5+6
[Example]
in case of refnet header: indoor units
1+2+3+4+5+6+7+8
Use the outdoor unit multi connection piping kit that is sold separately
as an option (BHFQ23P907+1357) for the multi installation of outdoor
units. Selection method is as shown in the right table.
ABCDE
abcd
e
8
H2
H1
H3
f
lnp
B1 B2 B3
B4
xy z
F
h
1
g
G
j
2
k
mo q r s
3
i
4 5 6 7
A
B
am
H2
H1
H3
b
B1 B2 B3
B4
n p
xy
z
d
1
fh
g
j
i
kl o
2 3 4 5 6 7
8
ce
B5
a
H2
H1
H3
B1 B2 B3 B4
xy
z
c
1
eg
f
i
hj l
no
2 3 4 5 6 7
8
k
bd
B2
B3
m
Outdoor unit side (3 pipes) Indoor unit side (2 pipes)
Suction gas pipe Gas pipe
HP/LP gas pipe BS unit
Liquid pipe Liquid pipe
indoor unit refnet header Outdoor unit side (3 pipes)
refnet joint outdoor multi connection piping kit Indoor unit side (2 pipes)
Refrigerant branch kits can only be used with R410A.