EDUS39-600-F5 Installation
FXHQ-M 33
L5
Instantaneous overcurrent (outdoor)
Compressor motor grounded or short circuit; inverter
PCB error
L8
Compressor overcurrent or compressor motor wire cut
L9
Compressor possibly locked
LC
Communication error between inverter and outdoor
control unit
P1 Open-phase (outdoor)
P3 PC board temperature sensor malfunction (outdoor)
P4 Radiation fin temperature sensor error
PJ
Capacity setting error (outdoor) or nothing pro-
grammed in the data hold IC.
U0
Low pressure drop due to insufficient refrigerant or
electronic expanison valve error.
U2
Power source voltage failure
U3
Failure to carry out check operation; transmission
error
U4
UF
Communication error due to incorrect wiring between
indoor unit and outdoor unit, or communication error
between outdoor unit and BS unit.
Failure to carry out check operation for indoor-outdoor
or outdoor-outdoor communications.
U9
Communication error between indoor and outdoor
unit, or BS unit and indoor/outdoor unit.
UA
nation error of indoor/BS/outdoor unit; setting error of
spare parts PCB when replaced.