FXHQ-M 27
Attach the plastic bushing (10) for remote controller wiring.
Insert the conduit for power supply wire in the conduit hole,
and fix it with the lock nut.
Power supply wire
Holding the control box lid, loosen the 2 securing screws,
remove the control box lid, match up the phases on the
power supply terminal block inside (2P), and make the con-
nections.
After this is done, use the attached clamp (4) to bind wire
between units to the anchor point. (Refer to Fig. 28)
Remote controller wire and transmission wire
Holding the control box lid, loosen the 2 securing screws,
remove the control box lid.
Thread the remote controller wire and transmission wire
through the conduit (11), secure with the clamp (4), and cut
off conduit (11) to suitable length. The conduit (11) can let
the wire pass to a maximum of 2 wires. If there are three
or more wires, use another conduit (11). Pull the wires
inside through plastic bushing and connect the wires to the
transmission terminal block (6P inside the control box. After
connecting, use the clamp (4) to bind the remote controller
wire together with the transmission wire to the anchor.
(Refer to Fig. 27, 28, 29)
The conduit (11) allows the remote controller wire and
transmission wire pass to a maximum of 2 wires.
WARNING
Never connect power supply wiring to the terminal block for
remote controller wiring as this could damage the entire sys-
tem.
Use only specified wire and connect wires to the terminal
tightly. Be careful wires do not place external stress on ter-
minals. Keep wires in neat order so as to not obstruct other
equipment. Make sure that the electric box lid fits tightly.
Incomplete connections could result in overheating and, in
worse cases, result in electric shock or fire.
Resin bush (10)
Lock nut
Conduit
Conduit hole
Fig. 26
L
1
POWER SUPPLY
L
2
power supply
How to connect power supply
terminal block (2P)
Control box
Transmission
terminal block (6P)
Power supply
teminal block (2P)
Remote controller wire
and transmission wire
Refer to Fig. 28
Ground terminal
Power supply wire
Gas pipe
Liquid pipe
Drain pipe
Conduit
Corking or Putty
Resin bush (10)
Control box
lid secuing screw (2 pcs.)
Control box lid
Insulating tube (11)
Clamp (4)
Fig. 27
Fastener
Clamp (4)
Clamp (4)
Ground wire
After securing the
cramp material
to the bracket,
cut off any extra
material.
Remote controller wire and
transmission wire
Fastener
Power supply wire
Fig. 28
P1 P 2 F1 F2 T1 T2
REMOTE
CNTRL
FORCED
OFF
TRANSMISSION
WIRING
Clamp (4)
Remote controller wire
Transmission
terminal block (6P)
Transmission wire
Insulating
tube (11)
1 in.
Fig. 29