EDUS39-600-F5 Installation
FXHQ-M 31
11-4 CENTRALIZED CONTROL
For centralized control, it is necessary to designate the
Group Number. For details, refer to the manual of each
optional controllers for centralized control.
Set the remote controller to the FIELD SET MODE. For
details, refer to HOW TO SET IN THE FIELD in the remote
controller manual.
When in the FIELD SET MODE, select mode No. 12, then
set the FIRST CODE NO. to [1]. Then set SECOND CODE
NO. to [01] for FORCED OFF and [02] for ON/OFF OPER-
ATI ON. (FORCED OFF at factory set)
12. TEST OPERATION
Refer to the section TAKE SPECIAL CARE DURING CON-
STRUCTION on page 185.
Make sure if the service lids are closed on the indoor and
outdoor units.
After finishing the construction of refrigerant pipe, drain
pipe, and electric wire, conduct the check operation by
referring to the installation manual of the outdoor unit.
The operation lamp of the remote controller will flash when
a malfunction occurs. Check the displayed malfunction
code to identify the trouble. An explanation of malfunction
codes and the corresponding trouble is provided in the
installation manual of the outdoor unit.
It any of the items in Table 6 are displayed, there may be a
problem with the wiring or power, so check the wiring again.
Ta b l e 6
•If U3 is lit up, the malfunction code shows the check oper-
ation has not been performed yet.
12-1 HOW TO DIAGNOSE FOR MALFUNCTION
With the power on, it is possible to monitor the type of
malfunction by looking at the malfunction code displayed
in the remote controller.
If nothing is displayed in the remote controller, check the fol-
lowing items before attempting a diagnosis based on the mal-
function code, as they might be a cause.
Disconnected or incorrect wiring (between power supply
and the outdoor unit, between the outdoor and indoor units,
and between the indoor unit and the remote controller)
Burnt out indoor or outdoor unit fuse
•“ will be displayed for a few seconds on the remote
controller immediately after the power is turned on.
This display indicates that the remote controller is being
checked to see whether it is ok or not, and does not indicate
a malfunction.
SETTING
Mode
No.
SECOND
CORD NO.
FIRST
CORD NO.
FIELD SET
MODE
Remote control display Content
Under Cen-
tralized Control is lit
There is a short circuit at the
FORCED OFF terminals (T1, T2).
U4 is lit
UF is lit
The power on the outdoor unit is
off.
The outdoor unit has not been
wired for power supply.
Incorrect wiring for the transmis-
sion wiring and / or FORCED OFF
wiring.
The transmission wiring is cut.
No display
The power on the indoor unit is off.
The indoor unit has not been wired
for power supply.
Incorrect wiring for the remote con-
troller wiring, the transmission wir-
ing and / or the FORCED OFF
wiring.
The remote controller wiring is cut.