Page 33 of 36 / OM 1169-1
Service Settings Menu
Indoor Unit Status (continued)
Indoor Unit Status Menu Items In Step 2.
FAN L or H Fan Speed
rpm: No data
FLAP: PO always
EV: 0pls always
MP: ON or OFF N/A ‒ ‒ unused output (drain pump)
EH: ON or OFF Electric heater state
Hu: OFF always
TBF: OFF always
Step 3.
Press ◄ to display the next “Indoor Unit Status” screen.
Indoor Unit Status
Unit No. 0
FLOAT: CLOSE T1/T2: CLOSE
–
–
Indoor Unit Status Menu Items In Step 3.
FLOAT Close/Open (Normally closed)
T1/T2 Open/Close (Normally open)
Step 4.
Press ◄ to display the next “Indoor Unit Status” screen.
Indoor Unit Status
Unit No. 0
Th1: ͞ ͞ F Th5 : 85F
Th2: 75F Th6 : 84F
Th3: 78F
Th4: ͞ ͞ F
–
Indoor Unit Status Menu Items In Step 4.
Th1: ‒ ‒ ‒ ‒
Th2:
R12T (white) between air coil and RV (Liquid
thermistor)
Th3:
R13T (yellow) - EEV side of air coil, bottom circuit
(Gas thermistor)
Th4: ‒ ‒ ‒ ‒
Th5: Remote controller thermistor
Th6:
Average of present control temp (R/C thermistor
and Return Air sensor, if any)
Th# menu descriptions
Th# Description
Th1 Return air sensor (Remote sensor) temperature
Th2 Liquid line temperature
Th3 Gas line temperature
Th4 Discharge air temperature (FXMQ_P only)
Th5 Remote controller sensor temperature
Th6
Temperature to be used for indoor unit control (See “Field
Setting” 10(20) - 2)
Step 5.
Press ◄ to display the next “Outdoor Unit Status” screen.
Outdoor Unit Status
Unit No. 0
FANstep: –––
COMP: –––––
EV1: ––––pls
SY1: ––
–
Outdoor Unit Status Menu Items In Step 5.
FANstep ‒ ‒ ‒ ‒
COMP ‒ ‒ ‒ ‒ Appears on screen (not adjustable)
EV1: ‒ ‒ ‒ ‒pls Appears on screen (not adjustable)
SV1: ‒ ‒ ‒ ‒ Appears on screen (not adjustable)
Forced Fan On
Note: Not Applicable with SmartSource Inverter WSHP unit.