Daikin BRC1E72 Guia de preparacion Pagina 21

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 36
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 20
Page 21 of 36 / OM 1169-1
Basic Operation
Auto Mode in Remote Controller
H → C:
Room temp. ≥ C_SP + 1°F (0.5°C)
C → H:
Room temp ≤ H _ SP − 1°F (0.5°C)
─ ─ ─ ─ ─ ─ ─ ─ ─ ─ ─ ─ H C
C_SP
+1°F (0.5°C)
H_SP
-1°F (0.5°C)
─ ─ ─ ─ ─ ─ ─ ─ ─ ─ ─ ─ C H
Note: C_SP and H_SP can be set independently keeping the
minimumsetpointdifferential(0-7°Fcongurable,2°F
default)
1 Hour Guard Timer
Upon changeover, guard timer will prevent another
changeover during this period
Guard timer can be overridden by a change of setpoint
manually or by schedule
Timer is congurable to 15, 30, or 90 minutes with the
eld setting
Dry Mode
Characteristics Of Dry Mode
The Dry Mode dehumidies the space at reduced cooling
capacity to prevent the room temperature from dropping to
uncomfortable levels. In Dry Mode, the system maintains
automatic temperature and fan speed control. The fan only
operates at low, regardless of whether the controller is set for
low or high fan speed.
On entering dry mode, the control system takes note of the
current Room Temperature (Tro).
If Tro > 76.1°F (24.5°C), the controller cycles on and off
in cooling mode to keep the room temperature between
Tro and (Tro-2.7°F).
If Tro ≤ 76.1°F, the controller cycles on and off in cool-
ing mode to keep the room temperature between Tro and
(Tro-1.8°F).
As shown in Figure 10, while in Dry Mode Operation, the fan
operates at low (L) ow rate, stops for a period of six minutes
while the thermostat is OFF, and then returns to operation at
(L) ow rate. (This control is used to prevent a rise in indoor
temperature while in thermostat OFF mode.)
Step 1.
Press Mode button several times until the Dry mode is selected.
Operation
Dry
Return Setting
Note: In Dry mode, the system maintains automatic tempera-
ture and fan speed control. Therefore, temperature
setpoint or fan speed settings are not available while
the WSHP unit is in the Dry mode.
Note: To prevent water damage or system failure, do not im-
mediately remove power from the WSHP unit following
systemoperation.Waitatleastveminutesforthe
condensatepumptonishdrainingresidualwaterfrom
the unit.
Figure 10: Dry Mode sequence of operation