Page 16 of 36 / OM 1169-1
Mode No.
(Note 1)
First Code
No.
Description
Second Code No. (Note 2) (Tinted cells are factory default settings)
01 02 03 04
22
0
KRP1B71 X1-X2
status output
Unit Thermistor On/Off
status.
Indoor unit operation
On/Off status
Unit Alarm status
1 Unit T1-T2 input
Forced Off
Closed Contact – Unit
is forced off and Central
Control icon is displayed.
Unit cannot be turned on
manually. Operation can
be overridden by central
control.
On/Off
Closed Contact–Unit is
turned off.
Unit responds to last com-
mand, i.e., unit can be
turned on manually or by
central control after circuit
has opened. Operation is
prohibited when remote
controller On/Off control is
restricted by a multi zone
controller.
External Protection
Device
Closed contact–unit
shall resume normal
operation.
Open contact–unit
shall shut down and
generate an A0 error.
2
Thermo-On/Off dead band
(Note 4).
2F (1C) 1F (0.5C)
3
Fan Speed in Heating Thermo-
Off
LL User set Off
6
Fan Speed in Cooling Thermo-
Off
LL User set Off
Notes: 1.NativeremotecontrollerScheduleandAuto-changeoverfunctionsaredisabledwhenamultizonecontrollerisdetected
and a group address is assigned.
2. Field settings are normally applied to the entire remote control group, however if individual units in the remote control group require
specicsettingsorforconrmationthatsettingshavebeenestablished,utilizethemodenumberinparenthesis.
3. Any features not supported by the installed unit will not be displayed.
4.Whenmode10-2-01isselected,onlythereturnairtemperaturevalueisreportedtothemultizonecontroller.
5. The actual default dead band value will depend upon the unit model.
Specic Field Settings Changes
Notes: 1 Refer to page13-14for a step by step procedure
for selecting the Mode Number and the First Code
Number, and changing the Second Code Number.
2. For the remainder of the Field Settings section [or
alternatively] In the next three sections, “Setting The
Fan Mode”, “Enabling Setback Temperature
Control”, and “Activating Filter Change Indicator”
Setting The Fan Mode
Continuous Or Auto On/Off
Factory Default Settings:
22-06-02: In cooling mode, when there is no call for cooling,
the fan runs continuously at the speed selected on the Remote
Controller.
22-03-01: In heating mode, when there is no call for heating,
the fan runs continuously at low speed.
Fan Off When Satised
Step 1.
Hold “Cancel” button for 5 seconds to display “Service
Menu”. Scroll down to “Field Settings”. Select by pressing
Menu/OK.
Setup Guide
Mode & Code Settings (Continued)
Step 2.
Press▲▼ buttons until the mode number reaches 22.
Press ◄► buttons until the space next to 06 is highlighted
(cooling mode)
Press▲▼ buttons until the number reads 03, and press Menu/
OK to select.
Select “Yes” when asked to save the settings, and press Menu/
OK to select.
Step 3.
Press ◄► buttons until the space next to 03 is highlighted
(heating mode)
Press ▲▼ buttons until the number reads 03, and press
Menu/OK to select.
Select “Yes” when asked to save the settings, and press Menu/
OK to select.
Step 4.
Press the “Cancel” button twice, and the basic screen returns.
Mode
First
Code No.
Description
Second Code No.
01 02 03
22
3
Fan Speed
in Heating
Thermo-Off
LL User set Off
6
Fan Speed
in Cooling
Thermo-Off
LL User set Off