INDOOR UNIT
FDYQ100KAV1 FDYQ125KAV1 FDYQ160KAV1
FDYQ180MV1 FDYQ200PV1 FDYQ250MV19
OUTDOOR UNIT
RZQ100HY4A RZQ125HY4A RZQ160HY4A
RZYQ7PY1 RZYQ8PY1 RZYQ10PUY1
Rated Capacity
Cool (kW) 10.0 12.5 14.5 18.0 20.0 24.6
Heat (kW) 12.1 14.9 16.3 20.0 22.4 28.0
Capacity Range
Cool (kW) 5.0-11.2 5.7-14.0 6.20-15.5 10.8-20.0 12.0-22.4 15.0-28.0
Heat (kW) 5.1-12.5 6.0-16.0 6.2-18.0 12.0-22.4 13.4-25.0 16.8-31.5
Power Input (Rated)
Cool (kW) 3.09 4.17 5.33 5.68 6.47 8.42
Heat (kW) 3.46 4.30 4.55 5.63 6.22 8.86
E.E.R./C.O.P. C/H 3.24/3.50 3.00/3.47 2.72/3.58 3.17/3.55 3.09/3.60 2.92/3.16
Air Flow Rate (Rated) l/s 815 900 1000 1180 1200 1400
Indoor Sound Level (@1.5m) dBA 46 48 51 51 51 51
ESP Settings STD/HI STD/HI
Indoor Fan Speeds HI/LO HI/LO
Dimensions
(H x W x D)
Indoor (mm) 360 x 1478 x 899 500 x 1210 x 910 500 x 1410 x 910 500 x 1410 x 910
Outdoor (mm) 1345 x 900 x 320 1680 x 930 x 765 1680 x 930 x 765 1680 x 1240 x 765
Weight
Indoor (kg) 59 65 66 77 87 98
Outdoor (kg) 108 205 205 285
Power Supply Ø/V/HZ 3 phase, 415V, 50Hz
Compressor Type Hermetically sealed scroll type
Refrigerant R410A
Refrigerant Control Electronic
Refrigerant Pipe Size
Liq (mm) Ø 9.5 (Flared) 9.5 (Brazed)
Gas (mm) Ø 15.9 (Flared) 19.1 (Brazed) 22.2 (Brazed)
Drain Pipe Size ID 25mm, OD 32mm BSP 3/4 inch Internal Thread
Supply Air Conn. mm 1152 x 243 (Flange) 827 x 376 (Flange) 939 x 376 (Flange)
Return Air Conn. mm 2 x 400 (Oval) 918 x 350 (Flange) 1118 x 350 (Flange)
Max Actual Pipe Length m 75 150
Max Level Difference m 30 50 (40 if outdoor unit is below)
Pre Charged Length m 30 0
Outdoor Operating Range
Cool (°CDB) -5 to 46 -5 to 43
Heat (°CWB) -15 to 15.5 -20 to 15.5
Outdoor Sound Level (H)
@ 1 Metre from front of unit
Pressure dBA (C/H) 49/51 50/52 57/57 57/57 60/60
EPA Sound Power Level dBA 65 66 67 – – –
FDYQ180/200/250MV1
FDYQ100/125/160KAV1
• Highstrengthgalvanizedsteelcasing.
• Designofindoorunitsallowsforinstallationintolimited
roof space.
• Canbedismantledforeasierinstallationinlimited
roof space.
• Microprocessor-controlledoperationandmonitoring.
FEATURES OF INVERTER OUTDOOR UNITS
• NightQuietModereducessoundlevelsevenfurther;to
be set by Daikin specialists. (FDYQ71-160 models require
an interface card).
• Re-designedReluctanceDCScrollCompressor
offers superior energy saving, performance, and
low noise operation.
• Intelligentdefrostforhighheatoutputatlowwinter
outdoor temperatures.
• PEcoatedheatexchangersforgreaterprotection
against corrosion.
• Upto150mofrefrigerantpipingallowsexibilityof
location (RZYQ7-10P) (RZQ100-160H:75m)
• DCFanMotor–PowerfulNeodymiummagnetsenables
superior, efficiencies to conventional types.
INDOOR UNIT
RZYQ7/8PY1
RZQ100/125/160HY4A
OUTDOOR UNIT