RZQ125C
Heating
3D059958
Indoor Outdoor temperature (°C DB)
EDB
-15 -10 -5 0 6
10
°C TC
(kW)
PI
( - )
TC
(kW)
PI
( - )
TC
(kW)
PI
( - )
TC
(kW)
PI
( - )
TC
(kW)
PI
( - )
TC
(kW)
PI
( - )
16.0 8.83 0.89 9.76 0.94 10.7 0.99 11.6 1.04 16.2 1.09 17.5 1.14
18.0 8.82 0.93 9.74 0.98 10.7 1.03 11.6 1.08 16.2 1.13 17.5 1.19
20.0 8.81 0.97 9.73 1.02 10.7 1.07 11.6 1.12 16.2 1.18 17.5 1.24
21.0 8.81 0.99 9.73 1.04 10.6 1.09 11.6 1.14 16.2 1.20 17.5 1.26
22.0 8.80 1.00 9.72 1.05 10.6 1.11 11.6 1.16 16.2 1.23 17.5 1.29
24.0 8.79 1.04 9.71 1.10 10.6 1.15 11.5 1.21 16.2 1.27 17.4 1.33
NOTES
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat.
2 On the figure the mark with show the max, onces at standard conditions.
On the figure the mark with show rated capacity and rated coefficient of power input.
However the max. Capacity is not guaranteed ecxept at standard condition.
3 SHC* is based on each EWB and EDB.
SHC= SHC correction for other dry bulb.
= 0.02xAFR (m
3
/min.)x(1-BF)x(DB*-EDB)
Add SHC to SHC*.
4 Capacities are based on the following conditions.
Outdoor air: 85% RH. However, the condition
rated capacity is 7°C DB/6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Heating performance include the drop of frost formation.
8 Air flow rate and (BF) are tabulated below.
9 Rated power input of each model is tabulated below.
(Pair) (Twin)
FCQH125C FCQ125C FBQ125 FHQ125 FUQ125 FDQ125 FCQ60Cx2 FFQ60x2 FBQ60x2 FHQ60x2
AFR
(BF)
32.5
(0.19)
27.5
(0.19)
35
(0.14)
30
(0.13)
32
(0.07)
45
(0.25)
AFR
(BF)
13.5x2
(0.21x2)
15x2
(0.11x2)
19x2
(0.11x2)
17x2
(0.2x2)
(Pair) (Double Twin)
FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 FCQ35Cx4 FFQ35x4 FBQ35x4 FHQ35x4
AFR
(BF)
12.5x3
(0.21x3)
15x3
(0.16x3)
12x3
(0.16x3)
14x3
(0.1x3)
AFR
(BF)
10.5x4
(0.28x4)
10x4
(0.25x4)
11.5x4
(0.15x4)
13x4
(0.2x4)
(Pair) (Twin)
FCQH125C FCQ125C FBQ125 FHQ125 FUQ125 FDQ125 FCQ60Cx2 FFQ60x2 FBQ60x2 FHQ60x2
Cooling 3.70 3.88 3.97 4.45 4.15 4.15 Cooling 4.08 4.12 4.18 4.45
Heating 3.57 3.95 3.98 4.36 4.33 3.67 Heating 4.16 4.25 4.19 4.59
(Triple)
(Double Twin)
FCQ50Cx3 FFQ50x3 FBQ50x3 FHQ50x3 FCQ35Cx4 FCQ35x4 FBQ35x4 FHQ35x4
Cooling 4.08 4.12 4.18 4.45 Cooling 4.08 4.12 4.18 4.45
Heating 4.16 4.25 4.19 4.59 Heating 4.16 4.25 4.19 4.59
SYMBOLS
AFR : Air flow rate (m3/mim.)
BF : Bypass factor
EWB : Entering wet bulb temp. (°C DB)
EDB : Entering dry bulb temp. (°C DB)
TC : Total cooling (heating) capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (Comp.+indoor+outdoor fan motor). (kW)
CPI : Coefficient of power input ( - )
Caution
:
TC and SHC are shown by kW.
Heating
Coefficient of power input ( - )
Heating Capacity (kW)
Rated point
Capacity range