RZQ100C
Cooling
3D059957
Indoor Outdoor temperature (°C DB)
EWB EDB
25 30 35 40
°C °C TC
(kW)
SHC
(kW)
CPI
( - )
TC
(kW)
SHC
(kW)
CPI
( - )
TC
(kW)
SHC
(kW)
CPI
( - )
TC
(kW)
SHC
(kW)
CPI
( - )
16.0 22 10.2 6.93 0.86 10.2 7.00 1.01 10.5 7.29 1.12 10.1 7.08 1.23
18.0 25 11.8 7.59 0.94 11.3 7.45 1.03 11.0 7.27 1.13 10.5 7.06 1.24
19.0 27 12.0 7.57 0.95 11.6 7.43 1.03 11.2 7.26 1.13 10.8 7.04 1.24
19.5 27 12.1 7.56 0.95 11.8 7.41 1.03 11.3 7.25 1.13 10.9 7.03 1.24
22.0 30 12.7 7.46 0.96 12.3 7.32 1.04 11.9 7.16 1.14 11.4 6.96 1.25
24.0 32 13.2 7.36 0.96 12.8 7.22 1.05 12.4 7.06 1.15 11.9 6.87 1.27
NOTES
1 Ratings shown are net capacities which include a deduction for indoor fan motor heat.
2 On the figure the mark with show the max, onces at standard conditions.
On the figure the mark with show rated capacity and rated coefficient of power input.
However the max. Capacity is not guaranteed ecxept at standard condition.
3 SHC* is based on each EWB and EDB.
SHC= SHC correction for other dry bulb.
= 0.02xAFR (m
3
/min.)x(1-BF)x(DB*-EDB)
Add SHC to SHC*.
4 Capacities are based on the following conditions.
Outdoor air: 85% RH. However, the condition
rated capacity is 7°C DB/6°C WB. (heating)
Corresponding refrigerant piping length : 5.0m
Level difference : 0m
5 Coefficient of power input is the percentage when the rated value is defined as 1.00.
6 The value contains less than 5% error acording to indoor unit type.
7 Heating performance include the drop of frost formation.
8 Air flow rate and (BF) are tabulated below.
9 Rated power input of each model is tabulated below.
(Pair) (Twin)
FCQH100C FCQ100C FBQ100 FHQ100 FAQ100 FUQ100 FCQ50Cx2 FCQ50Bx2 FFQ50x2 FBQ50x2
AFR
(BF)
32.5
(0.17)
23.5
(0.16)
27
(0.20)
24
(0.14)
23
(0.10)
29
(0.07)
AFR
(BF)
12.5x2
(0.21x2)
12x2
(0.16x2)
14x2
(0.15x2)
13x2
(0.1x2)
(Triple)
FCQ35Cx3 FFQ35Bx3 FBQ35x3 FHQ35x3
AFR
(BF)
10.5x3
(0.28x3)
10x3
(0.25x3)
11.5x3
(0.15x3)
13x3
(0.2x3)
(Pair) (Twin)
FCQH100C FCQ100C FBQ100 FHQ100 FAQ100 FUQ100 FCQ50Cx2 FFQ50x2 FBQ50x2 FHQ50x2
Cooling 2.66 2.77 3.00 3.30 3.45 3.12 Cooling 2.92 2.93 3.16 3.48
Heating 2.55 3.02 2.99 3.49 3.27 3.37 Heating 3.18 3.20 3.15 3.67
(Triple)
FCQ35Cx3 FFQ35x3 FBQ35x3 FHQ35x3
Cooling2.922.933.163.48
Heating3.183.203.153.67
SYMBOLS
AFR : Air flow rate (m3/mim.)
BF : Bypass factor
EWB : Entering wet bulb temp. (°C DB)
EDB : Entering dry bulb temp. (°C DB)
TC : Total cooling (heating) capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (Comp.+indoor+outdoor fan motor). (kW)
CPI : Coefficient of power input ( - )
Caution
:
TC and SHC are shown by kW.
Cooling
Coefficient of power input ( - )
Cooling Capacity (kW)
Rated point
Capacity range