EDUS39-900A-F11_a Installation
FXMQ-M 21
8-3 SPECIFICATIONS FOR FIELD SUPPLIED
FUSES AND WIRE
NOTE
1. Allowable length of transmission wiring between indoor/
outdoor units and between the indoor unit and the remote
controller is as follows.
(1) Outdoor unit – Indoor unit:
Max. 3280ft. (Total wiring length: 6560ft.)
(2) Indoor unit – Remote controller:
Max. 1640ft.
9. WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER
9-1 HOW TO CONNECT WIRINGS
(Remove the electrical components box lid and wire as shown
in the figure below.)
Routing power supply wiring and transmission wiring
Let the power supply wiring with a conduit pass through one of
the holes on the side cover, and let the transmission wiring
with a conduit pass through another hole.
For protection from uninsulated live parts, thread the power
supply wiring or the transmission wiring through the
included insulation tube and secure it with the included
clamp.
CAUTION
Be sure to attach the sealing material or putty (field sup-
plied) to hole of wiring to prevent the infiltration of water as
well as any insects and other small creatures from outside.
Otherwise a short-circuit may occur inside the electrical
components box.
When clamping the wires, be sure no pressure is applied to
the wire connections by using the included clamping mate-
rial to make appropriate clamps. Also, when wiring, make
sure the lid on the electrical components box fits snugly by
arranging the wires neatly and attaching the electrical com-
ponents box lid firmly. When attaching the electrical com-
ponents box lid, make sure no wires get caught in the
edges. Pass wiring through the wiring through holes to pre-
vent damage to them.
Make sure the remote controller wiring, the wiring between
the units, and other electrical wiring do not pass through
the same locations outside of the unit, separating them by
at least 2in., otherwise electrical noise (external static)
could cause mistaken operation or breakage.
[ PRECAUTIONS ]
1. Use round crimp-style terminals for connecting wires to
the power supply terminal block.
If unavailable, observe the following points when wiring.
Do not connect wires of different gauge to the same
power supply terminal.
(Looseness in the connection may cause overheating.)
Use the specified electric wire. Connect the wire securely
to the terminal. Lock the wire down without applying
excessive force to the terminal. (Tightening torque:
0.97ft·lbf ±10 %)
Model
Power supply wir-
ing
Remote controller wiring
Transmission wiring
Breaker
Size Wire Size
FXMQ72MVJU
15A
Size
must
comply
with
local
codes.
2-conductor,
stranded non-
shielded
copper cable/
PVC or vinyl
jacket
AWG
18-2,
Max: 1640 ft.
FXMQ96MVJU
Electrical
components
box lid
Transmission
wiring (*)
Ground wiring
Power supply
wiring (*)
(Field wiring)
Remote controller
wiring (*)
(Field wiring)
(Field wiring)
Wiring (*)
(Remote controller
and transmission)
Wire locking
bracket
Clamp
(accessory(8))
Conduit
(Field supply)
Lock nut
(Field supply)
Insulation tube
(accessory (2))
Clamp
(accessory (8))
Power supply wiring
or
Transmission wiring
(3in.)
Clamp (accessory (8))
Power supply
terminal block
Terminal block for
remote controller
Remote
controller wiring
X2M
X1M
Transmission wiring
Power supply wiring
and ground wiring
Insulation tube
(accessory (2))
Insulation
tube
(accessory (2))
Ground
terminal
Electric wire
Round crimp-style terminal
Attach insulation sleeve