ELECTRICAL SPECIFICATIONS
For indoor units only: FHYC35B7V1 FHYC45B7V1 FHYC60B7V1
CURRENT Nominal running current
cooling
A
See chapter R(E)Y: Electrical data
heating
A
Max. running current
cooling
A
heating
A
For combination indoor units + outdoor units: FHYC35B7V1 FHYC45B7V1 FHYC60B7V1
RY35DA7V1 RY45DB7V1 RY60FA7V1
CURRENT Nominal running current
cooling
A 6.8 8.9 10.9
heating
A 6.3 8.1 10.7
Maximum running current
cooling
A 8.8 11.5 13.5
heating
A 8.8 11.5 13.5
Starting current
cooling
A353953
heating
A353953
For indoor units only: FHYC35B7V1 FHYC45B7V1 FHYC60B7V1
POWER SUPPLY V1 V1 V1
NOMINAL DISTRIBUTION
SYSTEM VOLTAGE
Phase 1 1 1
Frequency Hz 50 50 50
Voltage V 230 230 230
ELECTRICAL SPECIFICATIONS
For indoor units only: FHYC71B7V1 FHYC100B7V1 FHYC125B7V1
CURRENT Nominal running current A 0.7 0.9 0.9
Max. running current A See chapter R(E)Y: Electrical data
For combination indoor units + outdoor units: FHYC71B7V1 FHYC100B7V1 FHYC125B7V1
RY71B7V1/W1 RY100B7V1/W1 RY125B7W1
CURRENT Nominal running current
cooling
A
See chapter R(E)Y: Electrical data
heating
A
Maximum running current
cooling
A
heating
A
Starting current
cooling
A
heating
A
For indoor units only: FHYC71B7V1 FHYC100B7V1 FHYC125B7V1
POWER SUPPLY V1 V1 V1
NOMINAL DISTRIBUTION
SYSTEM VOLTAGE
Phase 1 1 1
Frequency Hz 50 50 50
Voltage V 230 230 230
NOTES
1 Nominal cooling capacities are based on: indoor temperature 27°CDB/19°CWB * outdoor temperature 35°CDB * refrigerant piping length: 7.5m *
level difference: 0m.
2 Nominal heating capacities are based on: indoor temperature: 20°CDB * outdoor temperature: 7°CDB/6°CWB * refrigerant piping length: 7.5m *
level difference 0m.
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 The sound pressure level is measured in an anechoic room at 1m distance from the unit. It is a relative value, depending on the distance and
acoustic environment. For measuring conditions: please refer to item 6 of this chapter.
5 The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.
4-Way Blow Ceiling Mounted Cassette R-22 FH(Y)C35-125B7
2
Specifications
13
2
8
Split - Sky Air Indoor Units