English 14
Table 3
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
NOTES
The above Table 3 of Electrical Characteristics refers to one BS unit.
See the Engineering data book for other details.
7-4 WIRING EXAMPLE
Here is shown a wiring example for one system transmission wiring.
Connect terminals F1 and F2 (TO IN/D UNIT) on the control PCB (A1P) in the outside unit Electrical Com-
ponents Box and terminals F1 and F2 (TO OUT/D UNIT) of the control PCB (A1P) of the first BS unit A.
NOTE
1. Connect cooling-dedicated air conditioners to terminals F1 and F2 (TO OUT/D UNIT) of the final BS unit.
2. Use 2-core wire for the transmission wiring. Using a multi-core wire with 3 or more cores when two or more
indoor units are used at once could cause abnormal stoppage. (Only use 3-core wire in the COOL/HEAT
SELECTOR.)
3. Absolutely do not connect the power supply wiring to the transmission wiring terminal block. Doing so
could damage the entire system.
4. For the transmission wiring, use wire that is within the following ranges. Exceeding these limits could
cause a transmission error.
(1) Between an outside unit and BS unit,
Between a BS unit and indoor unit, and
Between a BS unit and BS unit
Maximum wiring length: 3280 ft or less
Total wiring length: 6560 ft or less
Branch point max: 16 branch points
(2) Between a BS unit and COOL/HEAT SELECTOR
Maximum wiring length: 1640 ft or less
Units Power supply
Model Type Hz Voltage Min. Max. MCA MFA
BSVQ36P
BSVQ60P
BSVQ96P
VJ 60 208~230 187 253 0.1 15
F1F2
F1
F1 F2 F1 F2 F1 F2 F1 F2
F1 F2
F1 F2
F2 F1 F2
F1F2
F1 F2 F1 F2 F1 F2 F1 F2
A
ABC ABC ABC
B
C
A
B
C
A
B
C
(1)
(1)
(1) (1)
(1) (1) (1)
(1)
(1)
(2)(2)(2)
Absolutely do not
connect the power
supply wiring.
Transmission wiring
Use 2-core wires.
(There is no polarity.)
COOL/HEAT SELECTOR wiring
Use 3-core wires. (There is polarity.
Match the terminal numbers.)
Cooling/Heating selectable indoor unit
Cooling-dedicated
indoor unit
Outside unit
BS unit A BS unit B Final BS unit
C/H SELECTOR
COOL/HEAT
SELECTOR
COOL/HEAT
SELECTOR
COOL/HEAT
SELECTOR
C/H SELECTOR
C/H SELECTOR
TO IN/D UNIT
TO OUT/D UNIT
TO IN/D UNIT
TO OUT/D UNIT
TO IN/D UNIT
TO OUT/D UNIT
TO IN/D UNIT
TO OUT/D UNIT
F1 F2 F1F2
F1F2
F1F2
F1F2
branch
Sub-branching