Control box
Wiring connections for power supply quantity 3
remark Earth wire included
for connection with indoor quantity 2
remark F1-F2
for remote control quantity 2
remark P1,P2
for expansion valve kit quantity 6
remark Y1~Y6
thermistors liquid pipe quantity 2
remark R1,R2
thermistors gas pipe quantity 2
Remark R3,R4
thermistor air Quantity 2
Remark R5,R6
ON/OFF Remark T1,T2
Power Supply Intake Bottom
p. 31
2
COMBINATION TABLE
Combination table
CONTROL BOX EXPANSION VALVE KIT
Outdoor unit CONTROL Z CLASS 50 CLASS 63 CLASS 80 CLASS 100 CLASS 125 CLASS 140 CLASS 200 CLASS 250
EKEXMCB EKEXV50 EKEXV63 EKEXV80 EKEXV100 EKEXV125 EKEXV140 EKEXV200 EKEXV250
RXQ5P x x x x x x x x x
RXQ8P x x x x x x x x x
3ph RXQ10P x x x x x x x x x
RXQ12P x x x x x x x x x
RXQ14PA x x x x x x x x x
RXQ16PA x x x x x x x x x
RXQ18PA x x x x x x x x x
X = Quantity determined by connection ratio or maximum number of indoor units (the EKEVX-kit is considered as one of the indoor units
4
CONTROL BOX
Control box
Casing colour White grey
Dimensions unit height mm 132
width mm 400
depth mm 200
Weight unit kg 3.5
Operation Range cooling min °CDB -5.0
max °CDB 46.0
Power Supply name V3
phase 1
frequency Hz 50
voltage V 230
voltage range minimum V -10%
maximum V 10%
2. EXPANSION VALVE KIT (EXV)
3
Casing colour Ivory White
Dimensions unit height mm 401
width mm 215
depth mm 78
Weight unit kg 2.9
Piping Connection liquid mm 9.52
Sound Pressure Level nominal dB(A) 45 (max. at 10cm from motor)
Operation Range cooling min °CDB -5.0
max °CDB 46.0
s p e c i f i c a t i o n s
Expansion valve kit
EPCEN07-203:EPCEN07-203 19/07/07 12:46 Page 31