13 English
OPERATION MODE
The following five operation control modes can be selected along with the temperature setting and operation mode
by remote controller, for a total of twenty different modes. These twenty modes are set and displayed with control
modes of 0 to 19. (For further details, see EXAMPLE OF OPERATION SCHEDULE on the next page.)
• ON/OFF control impossible by remote controller..... Use this mode when operating and stopping from the
central remote controller only. (ON/OFF control by the
remote controller is disabled.)
• Only OFF control possible by remote controller ...... Use this mode when executing the operation only by the
central remote controller, and executing only the stop by
remote controller.
• Centralized .............................................................. Use this mode when executing the operation only by the
central remote controller, and executing start/stop freely
by remote controller during the preset hours.
• Individual ................................................................. Use this mode when executing start/stop both by central
remote controller and remote controller.
• Timer operation possible by remote controller......... Use this mode when executing start/stop by remote con-
troller during the preset hours, and not starting operation
by the central remote controller at the programmed time
of system start.
[HOW TO SELECT THE CONTROL MODE]
• Select whether to accept or to reject the operation from the remote controller regarding the operation, stop, tem-
perature setting and operation mode setting, respectively, and determine the particular control mode from the
rightmost column of the table below.