OPERATION MANUAL EWAQ080DAYNEWAQ100DAYNEWAQ130DAYNEWAQ150DAYNEWAQ180DAYNEWAQ210DAYNEWAQ240DAYNEWAQ260DAYN Packaged air-cooled water chillers
Operation manual9EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1CSwitching the unit offIf no remote on/off switch is configured:Press the œ
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual10•CAN STARTUP: the circuit is ready to start up when extracooling load i
Operation manual11EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1CAdvanced features of the digital controllerThis chapter gives an overvie
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual12PUMPFLOATING SETPOINTLANGUAGETIME AND DATEFREE COOLINGDICNADVANCEDDEFROS
Operation manual13EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1CHistory menu ‚The "history" menu contains all the information
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual14User password menu ÆNetwork menu ∆The "network" menu (only ava
Operation manual15EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1CSubmenu: CompressorDefining the lead-lag settingsIn the COMPR.LEAD-LAG sc
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual16Submenu: LanguageDefining the languageThis screen allows the user to defin
Operation manual17EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1CDefining controller settingsThe second ADVANCED screen of the usersetting
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual18Tasks of the info menuConsulting additional unit information1 Enter the
Operation manual 1 EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1C C ONTENTS Page Introduction ...
Operation manual19EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1CTasks of the login/logout menuChanging the user passwordAccess to the us
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual20When a safety device was activated, stop the unit and find out whythe saf
Operation manual21EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1C5.65.75.85.9a5.9b5.105.115.12Symptom 5.6: Superheat temperature is not
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual22Symptom 6: Unit stops soon after operation6Symptom 7: Sensor error 0C9/0
Operation manual23EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1C Water supply• Check if the water connection is still well fixed.• Check
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual24NOTES
Operation manual25EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1CANNEX IThermostat parametersWater temperature controlThe figures below sh
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual26ANNEX IIFloating setpoint workingThe diagrams and table below show the d
Operation manual27EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1CANNEX IV _v¶… ≤0U4∞11 ∞12 ≠H 012$0¢∞21 ∞22 ≠H013£6¢ªÒµ®†Úæ∂Ï_÷COOL.
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual28_÷ C2 ACT. PRESSURESHP2:019$0b = 050$8¢LP2:004$4b = -05$2¢ FAN
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual 2 Electrical specifications (1) General EWAQ 240 260 Dimensions HxWxD (m
4PW35556-1CCopyright © Daikin
Operation manual 3 EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1C Important information regarding the refrigerant used This product con
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual4Function of the main componentsFigure - Functional diagramAs the refriger
Operation manual5EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1C EvaporatorThe main function of the evaporator is to take heat from thew
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual6Internal wiring - Parts tableRefer to the internal wiring diagram supplie
Operation manual7EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1CT1V...** ...Voltage transducer (only for option OP57)TR1 .
EWAQ080~260DAYNPackaged air-cooled water chillers4PW35556-1COperation manual8OPERATIONThe EWAQ units are equipped with a digital controller (locatedbe