Installation manual
4
4PW23710-1A
BRC7E530+531W8
Wireless remote controller kit
6
Refer to figure 9. Connect the harness from the
transmitter board to the connector X24 on the indoor
unit PC board.
F
IELD
SETTING
If optional accessories are mounted on the indoor unit,
the indoor unit setting may have to be changed. Refer to
the instruction manual (optional hand book) for each
optional accessory.
(See figure 4)
Procedure
1
When in normal mode, press the
button for
a minimum of four seconds, and the FIELD SET
MODE is entered.
2
Select the desired MODE NO. with the button.
3
Push the
button and select the FIRST CODE NO.
4
Push the
button and select the SECOND CODE
NO.
5
Push the button and the present settings
are SET.
6
Push the
button to return to the NORMAL
MODE.
Example
If the time to clean air filter is set to “Filter Contamination-Heavy”, set MODE NO. to “
10
”, FIRST CODE NO. to “
0
”,
and SECOND CODE NO. to “
02
”.
A
Be sure to pass only the harness
connecting to the indoor unit PC board
under the tab.
B
Be sure to wire the harness as shown to
avoid the harness to be caught by the
control box and the control box lid.
C
Position of the connector in the case of the
VRV system.
A
MODE NO.
B
FIELD SET MODE
C
FIRST CODE NO.
D
SECOND CODE NO.
MODE
NO.
FIRST
CODE
NO.
Description of setting
SECOND CODE NO.
1
00
00
11
11
00
00
22
22
00
00
33
33
10
0
Filter Contamination-Heavy/Light
(Setting for spacing time of display time
to clean air filter) (Setting for when filter
contamination is heavy, and spacing
time of display time to clean air filter is to
be halved)
Long-life
type
Light
±2500
hours
Heavy
±1250
hours
—
3
Spacing time of display time to clean air filter count
(Setting for when the filter sign is not to be
displayed)
Display Do not display —
12
(VRV
system)
1
ON/OFF input from outside (Set to enable starting/
stopping from remote.)
Forced OFF
input
ON/OFF —
2
Thermostat differential changeover (Set when using
remote controller thermostat sensor.)
1°C 0.5°C —
13
1
Selection of Air Flow Direction (Setting for when a
sealing member of air discharge outlet kit has been
installed)
FTW
4
Air Flow Direction Range Setting
Upper Normal Lower
1
NOTE
The SECOND CODE NO. is factory set to “
01
”. However, for the following cases it is set to “
02
”.
• Air Flow Direction Range Setting
Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial settings for all the indoor units of the group are equal. (For
group control, refer to the installation manual attached to the indoor unit for group control.)