Installation manual BRC1E52B7
19
4PW72364-1 – 11.2011
Remote controller display Description
No display
● Power outage, power voltage error or open-phase
● Wrong wiring (between indoor and outdoor units)
● Indoor PC-board assembly failure
● Remote controller wiring disconnection
● Remote controller failure
● Fuse blown (outdoor unit)
Display of "Checking the connection
Please stand by" is turned on. *
● Indoor PC-board assembly failure
● Wrong wiring (between indoor and outdoor units)
* Though "Checking the connection
Please stand by" is displayed for 90 seconds at maximum after power-on, this does not mean a failure.
(Determine after 90 seconds.)
8. Checking procedure of Error History
8-1 Press and hold Cancel button for
4 seconds or longer in the basic
screen. Service Settings menu is
displayed.
8-2 Select Error History in the Service
Settings menu, and press Menu/Enter
button. The Error History menu screen
is displayed.
8-3 Select RC Error History in the Error
History menu, and press Menu/Enter
button.
Error codes and unit No. can be
conrmed in the error record display
screen.
8-4 In the Error History, 10 items from the
latest are displayed in order.
8-5 Press Cancel button in the Error
History display screen 3 times.
The basic screen returns.
8-1 <Basic screen>
<Service Settings menu screen>
8-2
Return Setting
Service Settings
Indoor unit AirNet Address
Outdoor unit AirNet Address
Error History
Indoor Unit Status
Outdoor Unit Status
Forced Fan ON
1/3
Press Menu/Enter button.
8-3
Return Setting
Error History
RC Error History
Indoor unit Error History
2/2
Press Menu/Enter button.
8-4
8-5
Return
RC Error History
Unit Error Date Time
01
–– –– ––
/
––
/
–– ––:––
02
–– –– ––
/
––
/
–– ––:––
03
–– –– ––
/
––
/
–– ––:––
04
–– –– ––
/
––
/
–– ––:––
1/3
Unit No.
Latest record