MODELSCeiling-mounted Cassette type (Multi flow model)FCQ24MVJUFCQ30MVJUFCQ36MVJUFCQ42MVJUSPLIT SYSTEM Air ConditionersINSTALLATION MANUALRead these i
10NOTE• The incline of attached drain hose (1) should be 2 15/16 in. or less so that the drain socket does not have to stand addi-tional force.Select
119-2 ELECTRICAL CHARACTERISTICSMCA: Min. Circuit Amps (A) MFA: Max. Fuse Amps (A) KW: Fan Motor Rated Output (kW) FLA: Full Load Amps (A)9-3 SPEC
12WARNING• Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire sys-tem.• Use only spe
1310-3 CONTROL BY 2 REMOTE CONTROLLERS (Controlling 1 indoor unit by 2 remote controllers)• When using 2 remote controllers, one must be set to “MAIN”
1413. TEST OPERATION Refer to the section of “FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED.
1513-3 MALFUNCTION CODE• For places where the Malfunction code is left blank, the “ ” indication is not displayed. Though the system contin-ues operat
1645 Wallace Drive, Suite 110Carrollton, TX [email protected](0510) HT3PN06240-3E EM04A053C00_CV_3PN06240-3E (A4 Letter).fm Page
2SPLIT SYSTEM Air Conditioners Installation manualCONTENTS1. SAFETY CONSIDERATIONS...22. BEFORE INSTALLATION ..
3• Do not install the air conditioner in the following loca-tions:(a) where a mineral oil mist or an oil spray or vapor is pro-duced, for example in a
42-1 ACCESSORIESCheck the following accessories are included with your unit.2-2 OPTIONAL ACCESSORIES• The optional decoration panel and remote control
5DANGER• Do not install unit in an area where flammable materials are present due to the risk explosion resulting in serious injury or death.WARNING•
6(2) Make the ceiling opening needed for installation where applicable. (For existing ceilings)• Refer to the paper pattern for installation (5) for c
76. INDOOR UNIT INSTALLATIONInstalling optional accessories (except for the decoration panel) before installing the indoor unit is easier. However, fo
87-2 Connecting the refrigerant pipe• When connecting the flare nut, coat the flare both inside and outside with ester oil or ether oil and initially
97-4 Brazing refrigerant piping• Before brazing local refrigerant pipe, nitrogen gas shall be blown through the pipe to expel air from the pipe.If you